Functions
2.6 Circuit-Breaker Failure Protection 50BF
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
108
2.6.2
Setting Notes
General
The circuit-breaker failure protection and its ancillary functions (end fault protection, pole discrepancy supervi-
sion) can only operate if they were set during configuration of the scope of functions (address
139
50BF
, setting
Enabled
or
enabled w/ 3I0>
).
Breaker Failure Protection (50BF)
The breaker failure protection is switched
ON
or
OFF
at address
3901
FCT 50BF Break.
.
The current threshold
50BF PICKUP
(address
3902
) should be selected such that the protection will operate
with the smallest expected fault current. A setting of 10 % below the minimum fault current for which breaker
failure protection must operate is recommended. On the other hand, the value should not be set lower than
necessary.
If the breaker failure protection is configured with zero sequence current threshold (address
139
=
enabled
w/ 3I0>
), the pickup threshold for the zero sequence current
50NBF PICKUP
(address
3912
) can be set in-
dependently of
50BF PICKUP
.
Normally, the breaker failure protection evaluates the current flow criterion as well as the position of the breaker
auxiliary contact(s). If the auxiliary contact(s) status is not available in the device, this criterion cannot be pro-
cessed. In this case, set address
3909
Chk BRK CONTACT
to
NO
.
Two-Element Breaker Failure Protection
With two-element operation, the trip command is repeated after a time delay T1 to the local feeder breaker,
normally to a different set of trip coils of this breaker.
If the circuit breaker does not respond to this trip repetition, the adjacent circuit breakers are tripped after T2,
i.e. the circuit breakers of the busbar or of the concerned busbar section and, if necessary, also the circuit
breaker at the remote end unless the fault has been cleared.
The time delays can be set separately
• for trip repetition to the local feeder circuit breaker after a trip of the feeder protection
50BF-1 Delay 3p
(address
3905
),
• for trip of the adjacent circuit breakers (busbar zone and remote end if applicable)
50BF-2 Delay
at
address
3906
.
The time delays to be set should be based on the maximum circuit-breaker operating time plus the dropout time
of the current flow monitoring element plus a safety margin which takes into consideration the tolerance of the
time delay. Figure 2-43 illustrates the time sequences in an example. The dropout time for sinusoidal currents
is
≤
15 ms. If current transformer saturation is anticipated, the time should be set to 25 ms.
Note
To prevent automatic reclosing after
„50BF BusTrip“
, you can set the time
3408
T-Start MONITOR
so
that it elapses together with
50BF-2 Delay
.