8.6
Layout of the components
8.6.1
General
The arrangement of the components and equipment takes account of
● Space requirements
● Cable routing
● Bending radii of connecting cables
– For MOTION-CONNECT cables, see catalogs D21.4, D31.1 and NC62
– Hybrid cable: static 60 mm, dynamic 112.5 mm (≥7.5 · D with D = 14.6 ±0.4 mm)
● Heat dissipation
● EMC
The central components of the drive line-up should preferably be installed on a conductive
mounting surface to ensure a low impedance between the component and the mounting
surface. Mounting plates with a galvanized surface are suitable.
Components are usually located centrally in a cabinet. The necessary mounting and
installation clearances above an below the components can, under certain circumstances,
exceed the minimum clearances specified in the product documentation.
The components can be arranged in one or more tiers. In a multiple-tier arrangement, vertical
installation or, in a cabinet row, side-by-side installation in different cabinet sections is possible.
To determine the cross-section, use the DC link busbar current carrying capacity specified in
the relevant technical data.
A ventilation clearance of 100 mm must be maintained around the line reactor (not including the
mounting surface).
8.6.2
Current carrying capacity of the DC link busbar
The current carrying capacity of the DC link busbar must be observed for the configuration and
arrangement of the drive line-up.
Table 8-11
Maximum current carrying capacity of the DC link busbar
Current carrying capacity of
the DC link busbar
Components
100 A
● Motor Modules from 50 mm to 100 mm wide
● DC link components
150 A
● Motor Modules from 50 mm to 100 mm wide with reinforced DC link
busbars
200 A
● Motor Modules from 150 mm to 300 mm wide
Control cabinet design
8.6 Layout of the components
150
Manual, 06/2019, 6SL3097-5AW00-0BP1
Содержание Sinamics S120M
Страница 1: ...Equipment Manual Distributed drive technology Edition www siemens com drives 06 2019 S120M SINAMICS ...
Страница 2: ......
Страница 20: ...Introduction 1 8 General Data Protection Regulation 18 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Страница 32: ...Fundamental safety instructions 2 4 Residual risks of power drive systems 30 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Страница 56: ...System overview 3 5 System Data 54 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Страница 110: ...S120M 5 11 Motor holding brake 108 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Страница 118: ...DRIVE CLiQ Extension 6 6 Technical data 116 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Страница 126: ...Hybrid Cabinet Bushing 7 6 Technical data 124 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Страница 182: ...Appendix A 2 Documentation overview 180 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Страница 185: ......