Note
Protection against condensation and electrically conductive contamination
To ensure functional safety and safety functions of Safety Integrated, protect the AM600 and
the other components of the drive line-up, e.g. by installation in a control cabinet with degree
of protection IP54 according to IEC 60529 or Type 12 according to NEMA 250. Further
measures may be necessary for particularly critical operating conditions.
A lower degree of cabinet protection is permissible, if condensation and conductive pollution
can be excluded at the installation site.
A prefabricated hybrid cable for transferring power, the auxiliary power and DRIVE-CLiQ can
be ordered for the S120M.
Establish the connection between the following components using the hybrid cable (with
prefabricated, identical hybrid connectors at both ends of the cable):
● Adapter Module 600 - distributed drive line (S120M)
● Adapter Module 600 - Hybrid Cabinet Bushing
● Hybrid Cabinet Bushing - distributed drive line (S120M)
● S120M - S120M
● S120M - DRIVE-CLiQ Extension
Control cabinet design
8.1 General
126
Manual, 06/2019, 6SL3097-5AW00-0BP1
Содержание Sinamics S120M
Страница 1: ...Equipment Manual Distributed drive technology Edition www siemens com drives 06 2019 S120M SINAMICS ...
Страница 2: ......
Страница 20: ...Introduction 1 8 General Data Protection Regulation 18 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Страница 32: ...Fundamental safety instructions 2 4 Residual risks of power drive systems 30 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Страница 56: ...System overview 3 5 System Data 54 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Страница 110: ...S120M 5 11 Motor holding brake 108 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Страница 118: ...DRIVE CLiQ Extension 6 6 Technical data 116 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Страница 126: ...Hybrid Cabinet Bushing 7 6 Technical data 124 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Страница 182: ...Appendix A 2 Documentation overview 180 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Страница 185: ......