Commissioning
4.3 Connecting the inverter to the fieldbus
CU230P-2 Control Units
42
Compact Operating Instructions, 01/2016, A5E37058917B AA
Fault word according to the VIK-NAMUR definition (MELD_NAMUR), PZD send word 16 (word:
p2051[5], bits: r3113.00 … r3113.15)
Bit Meaning
0
0 = Control Unit has a no fault
1 = Control Unit fault
1
1 = line fault: Phase failure or inadmissible voltage
2
1 = DC link overvoltage
3
1 = Power Module fault, e.g. overcurrent or overtemperature
4
1 = inverter overtemperature
5
1 = ground fault/phase fault in the motor cable or in the motor
6
1 = motor overload
7
1 = communication error to the higher-level control
8
1 = error in a safe monitoring channel
10
1 = internal communication error in the inverter
11
1 = line fault
15
1 = other fault