Installing
3.4 Preassignment of the interfaces
CU230P-2 Control Units
Compact Operating Instructions, 01/2016, A5E37058917B AA
25
Default setting 105: "Fan pressure c ESM with fixed setpoint"
DO 0: p0730, …,
DO 2: p0732
AO 0: p0771[0], AO 1: p0771[1]
DI 0: r0722.0, DI 1: r0722.1 AI 0: r0755[0]
Additional settings:
•
Pressure control using the technology controller
•
Analog inputs smoothing time constant: p0753 = 500 ms
•
Technological unit: p0595 = 1 (%), reference variable: p0596 = 1
•
Fixed speed setpoint 15 for essential service mode (ESM): p1015 = 1350 rpm
•
Default setting of the technology controller:
–
Enable: p2200 = 1
–
Fixed value 1: p2201 = 40 %
–
Ramp-up/down time for setpoint: p2257 = p2258 = 30 s
–
Ramp-up/down time for controller output: p2293 = 30 s
–
Upper and lower limits, actual value: p2267 = 120 %, p2268 = -10 %
–
Actual value filter time constant: p2265 = 10 s
–
Proportional gain K
P
, integral time T
I
, differentiation time constant T
D
: p2280 (K
P
) = 1.1,
p2285 (T
I
) = 35 s, p2274 (T
D
) = 0 s
–
Technology controller minimum limiting p2292 = 20 %
–
Technology controller output signal start value p2302 = 50 %
•
"Flying restart" is enabled: p1200 = 1
•
Automatic restart is active. After a power failure, the inverter automatically acknowledges possible
faults and switches on the motor: p1210 = 26
Designation in BOP-2: P_F Pc5