Installing
3.4 Preassignment of the interfaces
CU230P-2 Control Units
22
Compact Operating Instructions, 01/2016, A5E37058917B AA
Default setting 101: "Universal application"
DO 0: p0730, …,
DO 2: p0732
AO 0: p0771[0], AO 1: p0771[1] DI 0: r0722.0, …, DI 5: r0722.5 AI 0: r0755[0]
Additional settings:
•
Fixed speed setpoint 1: p1001 = 800 rpm
•
Fixed speed setpoint 2: p1002 = 1000 rpm
•
Fixed speed setpoint 3: p1003 = 1200 rpm
•
If several of the DI 3 ... DI 5 = high, the inverter adds the corresponding fixed speeds.
•
Fixed speed setpoint 15 for essential service mode (ESM): p1015 = 1500 rpm
•
"Flying restart" is enabled: p1200 = 1
•
Automatic restart is active. After a power failure, the inverter automatically acknowledges possible
faults and switches on the motor: p1210 = 26
Designation in BOP-2: P_F 6PA