Installing
3.3 Terminal strips
CU230P-2 Control Units
Compact Operating Instructions, 01/2016, A5E37058917B AA
13
Additional options for wiring the digital inputs
Connecting P-switching contacts with an external
power supply
You must remove the jumper between
terminals 28 and 69 if it is necessary to
have electrical isolation between the
external power supply and the internal
inverter power supply.
Connecting M-switching contacts with an external
power supply
Remove the jumper between terminals
28 and 69.