Commissioning
4.2 Commissioning with BOP-2 operator panel
CU230P-2 Control Units
Compact Operating Instructions, 01/2016, A5E37058917B AA
35
8.2.
If you have selected a motor type > 100, then you must enter the
motor code:
With the correct motor code, the inverter assigns the motor data
the following values.
If you do not know the motor code, then you must set the motor
code = 0, and enter the motor data from p0304 and onwards from
the rating plate.
8.3.
87 Hz motor operation
The BOP-2 only displays this step if you previously selected IEC
as the motor standard (EUR/USA, P100 = KW 50HZ).
8.4.
Rated voltage
8.5.
Rated current
8.6.
Rated power
8.7.
Rated frequency
8.8.
Rated speed
8.9.
Motor cooling
SELF
Natural cooling
FORCED
Forced-air cooling
LIQUID
Liquid cooling
NO FAN
Without fan
9. Application and control mode
9.1.
Select the application:
VEC STD In all applications, which do not fit the other setting
options.
PUMP FAN Applications involving pumps and fans
SLVC 0HZ Applications with short ramp-up and ramp-down
times. However, this setting is not suitable for
hoisting gear and cranes/lifting gear.
PUMP 0HZ Setting only for steady-state operation with slow
speed changes. We recommend setting VEC STD
if load surges in operation cannot be ruled out.
The selection option depends on the Power Module being used. There is no se-
lection option for PM230 Power Modules.
9.2.
Select the control mode:
VF LIN
U/f control with linear characteristic
VF LIN F
Flux current control (FCC)
VF QUAD U/f control with square law characteristic
SPD N EN Vector control without encoder