Installing
3.1 Installation conditions
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
21
●
Terminal voltage, V
PR
–
max. 2000 V for 200 V converters
–
max. 2500 V for 400 V converters
●
Overvoltage category III
●
Pollution degree 2
●
Suitable for SPD applications, type 1 or type 2
Alternatively, use a surge protection device, article number 5SD7 424-1 from Siemens AG.
Additional requirements relating to CSA conformance, frame sizes FSD … FSG
Overvoltage category OVC III must be ensured for all connections of the power circuit. This
can mean that a surge suppressor must connected upstream on the line side. The rated
voltage of the surge suppressor must not exceed the line voltage, and must guarantee the
limit values (VPR) specified here.
Line voltage
Conductor
Phase to ground
Phase to phase
Rated
voltage
VPR
Rated
voltage
VPR
3 AC 200 V … 240 V
Grounded neutral con-
ductor
139 V
2.5 kV
240 V
4 kV
Grounded line conduc-
tor
240 V
4 kV
240 V
4 kV
3 AC 380 V … 480 V
Grounded neutral con-
ductor
277 V
4 kV
480 V
4 kV
Grounded line conduc-
tor
480 V
6 kV
480 V
4 kV
3 AC 500 V … 600 V
Grounded neutral con-
ductor
347 V
6 kV
600 V
4 kV
Grounded line conduc-
tor
600 V
6 kV
600 V
4 kV
Содержание SINAMICS G120
Страница 1: ...Power Module PM240 2 ...
Страница 2: ......
Страница 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 116: ...Technical data 6 9 Service life Power Module PM240 2 114 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 175: ......
Страница 176: ......