Technical data
6.4 200 V converters
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
85
Table 6- 12 PM240-2, PT, frame size E, 200 V to 240 V 3 AC
Article No. without filter
6SL3211-1PC31-1UL0
LO base load power
30 kW
LO base load input current
98 A
LO base load output current
104 A
HO base load power
22 kW
HO base load input current
83 A
HO base load output current
80 A
Fuse according to IEC
Fuse according to UL, class J
3NA3836 (160 A)
150 A
Power loss
1.28 kW
1)
Required cooling air flow
83 l/s
Weight
29.5 kg
1)
approx. 1.1 kW through the heatsink
Table 6- 13 PM240-2, IP20, frame size F, 200 V … 240 V 3 AC
Article No. without filter
6SL3210-1PC31-3UL0 6SL3210-1PC31-6UL0
6SL3210-1PC31-8UL0
LO base load power
37 kW
45 kW
55 kW
LO base load input current
126 A
149 A
172 A
LO base load output current
130 A
154 A
178 A
HO base load power
30 kW
37 kW
45 kW
HO base load input current
110 A
138 A
164 A
HO base load output current
104 A
130 A
154 A
Fuse according to IEC
Fuse according to UL, class J
3NA3140 (200 A)
175 A
3NA3140 (200 A)
200 A
3NA3142 (224 A)
250 A
Power loss
1.38 kW
1.72 kW
2.09 kW
Required cooling air flow
153 l/s
153 l/s
153 l/s
Weight
58 kg
58 kg
58 kg
Содержание SINAMICS G120
Страница 1: ...Power Module PM240 2 ...
Страница 2: ......
Страница 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 116: ...Technical data 6 9 Service life Power Module PM240 2 114 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 175: ......
Страница 176: ......