Connecting
4.2 Connecting the line and motor cable at the converter
Power Module PM240-2
56
Hardware Installation Manual, 01/2020, A5E33294624B AL
4.2.2
Length of the motor cable
Always dimension the motor cable so that the ohmic losses are less than 5 % of the
converter power rating.
The permissible length of the motor cable also depends on the quality of the motor cable and
the converter pulse frequency. The values specified below are applicable for high quality
cables, such as CY100 or similar, and for the pulse frequencies set in the factory.
Technical data (Page 73)
If you set other pulse frequencies, then you must ensure that the EMC category is complied
with on the plant or system side.
EMC-compliant wiring is required in order that the converter complies with the EMC category
listed in the following table.
EMC-compliant installation of a machine or system (Page 22)
Carefully observe the following section for operation in the first environment:
Electromagnetic compatibility of variable-speed drives (Page 107)
Table 4- 1
Permissible lengths of motor connecting cables, converter FSA … FSC
EMC category
Second Environment, C2
No EMC category
Converter
with internal
C2 filter
with external
C1 filter, with-
out output
reactor
without filter,
without output
reactor
without filter,
with output reactor
Cable
Shielded
Shielded
Shield-
ed/unshielded
Shielded
Unshielded
200 V
50 m
---
150 m
150 m
225 m
400 V
50 m
1)
150 m
3)
150 m
150 m
225 m
1)
For a low-capacitance motor cable: FSB 100 m, FSC 150 m
2)
For a low-capacitance motor cable: FSA 150 m, FSB 100 m, FSC 100 m
3)
150 m for voltages in the range 380 V … 415 V,
100 m for voltages in the range 440 V … 480 V
Table 4- 2
Permissible cable lengths for the motor connection, FSD … FSE
EMC category Second Envi-
ronment, C2
No EMC category
Converter
with internal
C2 filter
with or without filter, with or
without output reactor
without filter, with two output
reactors in series
Cable
Shielded
Shielded
Unshielded
Shielded
Unshielded
200 V
150 m
200 m
300 m
350 m
525 m
400 V
150 m
200 m
300 m
350 m
525 m
690 V
100 m
200 m
300 m
---
---
Содержание SINAMICS G120
Страница 1: ...Power Module PM240 2 ...
Страница 2: ......
Страница 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 116: ...Technical data 6 9 Service life Power Module PM240 2 114 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 175: ......
Страница 176: ......