Accessories
8.12 dv/dt filter plus VPL
Power Module PM240-2
162
Hardware Installation Manual, 01/2020, A5E33294624B AL
Article number JTA: TEF1203
-0KB
-0LB
-0MB
Rated power
90 kW
132 kW
250 kW
Rated voltage (phase to phase)
690 V (+10%)
690 V (+10%)
690 V (+10%)
Rated output current (rms)
103 A
230 A
416 A
Maximum output current (rms)
160 A
70 A
104 A
Inductance (Tolerance ± 5%)
0.53 mH
0.37 mH
0.22 mH
Winding resistance
3 x 4.9 m
Ω
3 x 3.25 m
Ω
3 x 1.4 m
Ω
Nominal pulse frequency
2 kHz
2 kHz
2 kHz
Maximum pulse frequency
4 kHz
4 kHz
4 kHz
Output current maximum pulse fre-
quency
61.8 A
87.6 A
156 A
Maximum output frequency
150 Hz
150 Hz
150 Hz
Voltage drop
17.2 V
17.1 V
18.0 V
Rated DC link voltage
935 V
935 V
935 V
Maximum voltage rise at motor ter-
minals
1)
< 500 V/
μ
s
< 500 V/
μ
s
< 500 V/
μ
s
Maximum peak voltage at motor
terminals (phase to phase)
2) 3)
1350 V ... 1500 V
1350 V ... 1500 V
1350 V ... 1500 V
Maximum peak voltage at motor
terminals (phase to earth)
2)
1100 V
1100 V
1100 V
Maximum cable length filter - motor
(screened / unscreened)
3)
450 m / 650 m
525 m / 800 m
450 m / 650 m
525 m / 800 m
450 m / 650 m
525 m / 800 m
Terminal type
Busbar M8
Busbar M10
Busbar M10
Rated terminal cross section (load
circuit)
95 mm²
120 mm²
2x120 mm²
1x185 mm²
Rated terminal cross section (DC
link feedback)
4)
25 mm²
25 mm²
50 mm²
Degree of protection
5)
IP00
IP00
IP00
Ambient temperature
6)
-20°C to 40°C
-20°C to 40°C
-20°C to 40°C
Weight
77 kg
97 kg
172 kg
Connection
Metrical (mm² / Nm)
Imperial (AWG / lbf.in)
Line / motor cable
95 / 13.0
3/0 / 115
120 / 13.0
4/0 / 115
2 x 120 / 13.0
2 x 4/0 / 115
185 / 13.0
6/0 / 13.0
DC link
25 / 9.0
4 / 80
25 / 9.0
4 / 80
50 / 9.0
1 / 80
Ground
50 / 6.0
1 / 53
70 / 6.0
2/0 / 53
95 / 6.0
3/0 / 53
1)
Voltage rise according IEC/TS 60034-17
2)
Under nominal DC link voltage
3)
Maximum peak voltage at motor terminals < 1350V at cable length up to 450m screened or 650m unscreened Maximum
peak voltage at motor terminals < 1500V at cable length up to 525m screened or 800m unscreened
4)
Short-circuit-proof wiring is required
5)
Installing the filter in an enclosure is required
6)
Higher ambient temperatures up to 60°C allowed with current derating at 40°C, in the range 40…50°C with 1.5% per 1K
and in the range 50…60°C with 1.9% per 1K
Содержание SINAMICS G120
Страница 1: ...Power Module PM240 2 ...
Страница 2: ......
Страница 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 116: ...Technical data 6 9 Service life Power Module PM240 2 114 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 175: ......
Страница 176: ......