Installation
04/2005
SINAMICS G110 Operating Instructions
30
6SL3298-0AA11-0BP0
♦
Free from dents and holes.
♦
Made of metal (steel or aluminium).
♦
Must not be painted.
♦
Must be free from rust.
5. Apply coating of heatsink/thermal contact paste to the inverter’s flat plate.
6. Ensure that the contact paste is spread evenly over the rear surface of the
Flat Plate.
7. Mount the inverter using four M4 screws.
8. Ensure that the inverter is mounted securely and the M4 screws are
tightened to the correct torque of 2.5 Nm (22.12 lbf.in).
9. If required, connect the external heatsink on the other side of the rear
plate, ensuring an evenly spread thermal contact paste is apply.
10. When the installation is completed the effectiveness of the cooling should
be verified by a load test.
11. Check that there is no trip F0004.
Table 2-3
Flat Plate Power Losses and Thermal Specifications*
120 W
250 W
370 W
550 W
750 W
Operating temperature range (ºC)
-10 to +50
-10 to +40
Total losses (W)
22
28
36
43
54
Lineside and control losses (W)
9
10
12
13
15
Recommended thermal resistance
of heatsink (K/W)
3.0 2.2 1.6 1.2 1.2
Recommended output current (A)
0.9
1.7
2.3
3.2
3.9
*The losses given in Table 2-3 are applicable for units fitted with 25 m of screened cable
Содержание SINAMICS G110
Страница 1: ...Operating Instructions Edition 04 2005 sinamics SINAMICS G110 ...
Страница 10: ...Safety Instructions 04 2005 SINAMICS G110 Operating Instructions 10 6SL3298 0AA11 0BP0 ...
Страница 14: ...Overview 04 2005 SINAMICS G110 Operating Instructions 14 6SL3298 0AA11 0BP0 ...
Страница 72: ...Options 04 2005 SINAMICS G110 Operating Instructions 72 6SL3298 0AA11 0BP0 ...
Страница 78: ...Electro Magnetic Compatibility EMC 04 2005 SINAMICS G110 Operating Instructions 78 6SL3298 0AA11 0BP0 ...
Страница 86: ...List of Abbreviations 04 2005 SINAMICS G110 Operating Instructions 86 6SL3298 0AA11 0BP0 ...
Страница 90: ......
Страница 91: ......