Commissioning 04/2005
SINAMICS G110 Operating Instructions
44
6SL3298-0AA11-0BP0
3.4.2 Commissioning Overview
Depending on the variant and desired mode (see Table 3-3 on page 41), different
possibilities are available for the advanced commissioning. Table 3-4 below gives
an overview on how to:
¾
Change the motor base frequency
¾
Configure the frequency setpoint and command source only
Table 3-4
Commissioning Overview
Mode
Changing Motor
Base Frequency
(Section 3.4.3)
Basic Operation
(Sections 4.1 and 4.2)
Advanced
Commissioning
TERMINAL
Via DIP Switch
only, see 3.3
a.
Frequency setpoint
:
potentiometer on terminal 9.
b.
Command source
:
switches on terminals 3 – 6.
Not applicable
SERIAL
a. DIP switch, or
b. P0100, or
c. Manually enter
data
a.
Frequency setpoint
:
connect USS to terminals 8 & 9.
b.
Command source
: connect
USS to terminals 8 & 9.
After reconfiguration,
terminals 3 – 6 can also be
used as command source.
Note:
Ensure bus is terminated!
a. Quick commissioning,
see Section 0
b. Factory default, see
Section 3.4.5
c. External motor thermal
overload protection, see
Section 3.4.6
BOP
a. DIP switch, or
b. P0100, or
c. Manually enter
data
a.
Frequency setpoint
:
use arrow keys (MOP)
b.
Command source
:
use ON, OFF and REV keys.
Note:
See 3.3.2 and 3.4.1 on page
42 for more information on
using the BOP.
a. Quick commissioning,
see Section 0
b. Factory default, see
Section 3.4.5
c. External motor thermal
overload protection, see
Section 3.4.6
d. Parameter cloning, see
Section 3.4.7
STARTER
a. DIP switch, or
b. P0100, or
c. Manually enter
data
a.
Frequency setpoint
:
see STARTER on-line help.
b.
Command source
: see
STARTER on-line help.
After reconfiguration,
terminals 3 – 6 can also be
used as command source.
a. Quick commissioning,
see Section 0
b. Factory default, see
Section 3.4.5
c. External motor thermal
overload protection, see
Section 3.4.6
d. Parameters can be
saved in file and can be
written to other
inverters. See
STARTER
documentation.
NOTES
¾
The frequency setpoint (P1000) and the command source (P0700) have both to
be set correctly to operate the SINAMICS G110 inverter. Alternatively, P0719
can be set to a specific frequency setpoint and command source.
¾
Frequency setpoint and command source can be derived from different modes
(e.g. the frequency setpoint is provided via the BOP with P1000 = 1 and the
command source is set by the terminals with P0700 = 2).
Содержание SINAMICS G110
Страница 1: ...Operating Instructions Edition 04 2005 sinamics SINAMICS G110 ...
Страница 10: ...Safety Instructions 04 2005 SINAMICS G110 Operating Instructions 10 6SL3298 0AA11 0BP0 ...
Страница 14: ...Overview 04 2005 SINAMICS G110 Operating Instructions 14 6SL3298 0AA11 0BP0 ...
Страница 72: ...Options 04 2005 SINAMICS G110 Operating Instructions 72 6SL3298 0AA11 0BP0 ...
Страница 78: ...Electro Magnetic Compatibility EMC 04 2005 SINAMICS G110 Operating Instructions 78 6SL3298 0AA11 0BP0 ...
Страница 86: ...List of Abbreviations 04 2005 SINAMICS G110 Operating Instructions 86 6SL3298 0AA11 0BP0 ...
Страница 90: ......
Страница 91: ......