1
Introduction & Specifications
SIMPRO-100
22
PRIM-2400C
1.6
SIMPRO-100 Relay
Monitoring &
Reporting Features
In addition to the protection functions outlined
earlier, the SIMPRO-100 Relay offers advanced
measuring and monitoring capabilities including:
•
Extensive metering capabilities that provide
real-time operating data.
•
Configurable front-panel display that replaces
separate panel meters.
•
A load profiling function that records currents,
voltages, and RTD temperatures every
15 minutes for over 30 days.
•
Event and SER reports that offer detailed
information about electrical faults.
•
Motor start reporting that shows current,
voltage, and thermal element values through
60 seconds of motor start. Use this
information to validate transformer and cable
sizing and confirm motor starting simulations.
•
Motor start trending that shows average
accelerating times, maximum currents, and
minimum voltages for each of the past
eighteen 30-day periods.
•
Control equations that allow you to customize
the operation of contact inputs and outputs for
your specific applications, if necessary.
1.7
Relay Order Number
To obtain a quotation or place an order for a
SIMPRO-100 Relay, it is helpful to have a relay
part number. The following information helps you
create a part number for the SIMPRO-100 Relay
and provides some additional information that
you may wish to include when you place your
relay order.
1.7.1
Create a Relay Order
Number
The SIMPRO-100 Relay order number has the
following form:
The answers to the questions listed in Table 1.2
will determine the value of options a and b.
Table 1.2
SIMPRO-100 Relay Order Number
Creation Table
Example:
SIMPRO-100 Relay Order Number
Creation
The part number SIMPRO-100–N–V
describes a SIMPRO-100 Relay equipped
without internal RTD inputs and with ac
voltage inputs.
All SIMPRO-100 Relays are equipped with 1 A
and 5 A nominal CT inputs, a broad operating
range power supply (20 – 250 ± 20% Vdc < 15 VA
or 95 – 240 ± 10% Vac 50/60 Hz), a single analog
current output with settable range, six (6)
self-wetted contact inputs, and four (4)
programmable form-C contact outputs. For more
product operating range information, Section 1.9,
page 23.
Question
Then
1 Does your applications require 11 internal RTD
inputs?
a) Yes
b) No
a = R
a = N
2 Does your application require ac voltage inputs?
a) Yes
b) No
b = V
b = N
Содержание SIMPRO-100
Страница 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Страница 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Страница 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Страница 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Страница 50: ...4 Settings Calculation SIMPRO 100 48 PRIM 2400C Figure 4 2 Generic Thermal Limit Curves Cold Motor ...
Страница 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Страница 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Страница 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Страница 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Страница 147: ...SIMPRO 100 Control Equations Relay Logic B PRIM 2400C 145 Figure B 3 Display Message Variables ...
Страница 157: ...SIMPRO 100 Control Equations Relay Logic B PRIM 2400C 155 Figure B 16 Overvoltage Element Logic ...
Страница 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Страница 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Страница 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Страница 239: ......