C
Modbus
™
RTU Communications Protocol
SIMPRO-100
174
PRIM-2400C
01CB
yyyy
0
65535
1
01CC
Last Reset Time
hh, mm
0, 0
23, 59
1, 1
01CD
ssss
0
5999
1
• 0.01
01CE
Reserved
01CF
Reserved
PEAK DEMAND METERING
01D0
Ia Peak Demand
0
65535
1
01D1
Ib Peak Demand
0
65535
1
01D2
Ic Peak Demand
0
65535
1
01D3
In Peak Demand
0
65535
1
01D4
Ig Peak Demand
0
65535
1
01D5
3I2 Peak Demand
0
65535
1
01D6
kW3P Peak Demand
0 if no voltage option
0
65535
1
01D7
kVAR3P Peak Demand In
0 if no voltage option
0
65535
1
01D8
kVAR3P Peak Demand Out
0 if no voltage option
0
65535
1
01D9
kVA3P Peak Demand
0 if no voltage option
0
65535
1
01DA
Last Reset Date
mm, dd
1, 1
12, 31
1, 1
01DB
yyyy
0
65535
1
01DC
Last Reset Time
hh, mm
0, 0
23, 59
1, 1
01DD
ssss
0
5999
1
• 0.01
01DE
Reserved
01DF
Reserved
CURRENT MAX/MIN METERING
01E0
Ia Max Current
(FFFFh if reset)
0
65535
1
01E1
Ia Max Current Date
mm, dd (FFFFh if reset)
1, 1
12, 31
1, 1
01E2
yyyy (FFFFh if reset)
0
65535
1
01E3
Ia Max Current Time
hh, mm (FFFFh if reset)
0, 0
23, 59
1, 1
01E4
ssss (FFFFh if reset)
0
5999
1
• 0.01
01E5
Ia Min Current
(FFFFh if reset)
0
65535
1
01E6
Ia Min Current Date
mm, dd (FFFFh if reset)
1, 1
12, 31
1, 1
01E7
yyyy (FFFFh if reset)
0
65535
1
01E8
Ia Min Current Time
hh, mm (FFFFh if reset)
0, 0
23, 59
1, 1
01E9
ssss (FFFFh if reset)
0
5999
1
• 0.01
01EA
Ib Max Current
(FFFFh if reset)
0
65535
1
01EB
Ib Max Current Date
mm, dd (FFFFh if reset)
1, 1
12, 31
1, 1
01EC
yyyy (FFFFh if reset)
0
65535
1
01ED
Ib Max Current Time
hh, mm (FFFFh if reset)
0, 0
23, 59
1, 1
01EE
ssss (FFFFh if reset)
0
5999
1
• 0.01
01EF
Ib Min Current
(FFFFh if reset)
0
65535
1
Address
(hex)
Field
Sample
Low
High
Step
Type
Содержание SIMPRO-100
Страница 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Страница 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Страница 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Страница 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Страница 50: ...4 Settings Calculation SIMPRO 100 48 PRIM 2400C Figure 4 2 Generic Thermal Limit Curves Cold Motor ...
Страница 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Страница 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Страница 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Страница 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Страница 147: ...SIMPRO 100 Control Equations Relay Logic B PRIM 2400C 145 Figure B 3 Display Message Variables ...
Страница 157: ...SIMPRO 100 Control Equations Relay Logic B PRIM 2400C 155 Figure B 16 Overvoltage Element Logic ...
Страница 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Страница 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Страница 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Страница 239: ......