3. Measure the winding temperature and the insulation resistance of the winding in relation
to the machine enclosure. The winding temperature should not exceed 40° C during the
measurement. Convert the measured insulation resistances in accordance with the formula
to the reference temperature of 40° C. This thereby ensures that the minimum values
specified can be compared.
4. Read out the insulation resistance one minute after applying the measuring voltage.
Limit values for the stator winding insulation resistance
The following table specifies the measuring voltage and limit values for the insulation
resistance. These values correspond to IEEE 43‑2000 recommendations.
Table 7-1
Stator winding insulation resistance at 40° C
V
N
[V]
V
Meas
[V]
R
C
[MΩ]
U ≤ 1000
500
≥ 5
1000 ≤ U ≤ 2500
500 (max. 1000)
100
2500 < U ≤ 5000
1000 (max. 2500)
5000 < U ≤ 12000
2500 (max. 5000)
U > 12000
5000 (max. 10000)
U
rated
= rated voltage, see the rating plate
U
meas
= DC measuring voltage
R
C
= minimum insulation resistance at reference temperature of 40° C
Conversion to the reference temperature
When measuring with winding temperatures other than 40° C, convert the measuring value to
the reference temperature of 40° C according to the following equations from IEEE 43-2000.
(1)
R
C
= K
T
· R
T
R
C
Insulation resistance converted to 40° C reference temperature
k
T
Temperature coefficient according to equation (2)
R
T
Measured insulation resistance for measuring/winding temperature T
in °C
(2)
K
T
= (0.5)
(40-T)/10
40
Reference temperature in °C
10
Halving/doubling of the insulation resistance with 10 K
T
Measuring/winding temperature in °C
In this case, doubling or halving the insulation resistance at a temperature change of 10 K is
used as the basis.
● The insulation resistance halves every time the temperature rises by 10 K.
● The resistance doubles every time the temperature falls by 10 K.
Commissioning
7.4 Testing the insulation resistance and polarization index
SIMOTICS XP 1MD4/1MD5
64
Operating Instructions 05/2015
Содержание SIMOTICS XP 1MD4
Страница 2: ...13 07 2015 11 26 V8 00 ...
Страница 10: ...Table of contents SIMOTICS XP 1MD4 1MD5 10 Operating Instructions 05 2015 ...
Страница 12: ...Introduction SIMOTICS XP 1MD4 1MD5 12 Operating Instructions 05 2015 ...
Страница 20: ...Safety notes 2 11 Ventilation SIMOTICS XP 1MD4 1MD5 20 Operating Instructions 05 2015 ...
Страница 26: ...Description SIMOTICS XP 1MD4 1MD5 26 Operating Instructions 05 2015 ...
Страница 40: ...Preparations for use 4 10 Converter operation SIMOTICS XP 1MD4 1MD5 40 Operating Instructions 05 2015 ...
Страница 50: ...Assembling 5 3 Installing the machine SIMOTICS XP 1MD4 1MD5 50 Operating Instructions 05 2015 ...
Страница 74: ...Operation 8 7 Faults SIMOTICS XP 1MD4 1MD5 74 Operating Instructions 05 2015 ...
Страница 90: ...Maintenance 9 2 Repair SIMOTICS XP 1MD4 1MD5 90 Operating Instructions 05 2015 ...
Страница 110: ...Disposal 11 4 Disposal of components SIMOTICS XP 1MD4 1MD5 110 Operating Instructions 05 2015 ...
Страница 126: ...Index SIMOTICS XP 1MD4 1MD5 126 Operating Instructions 05 2015 ...
Страница 127: ...AE EC Declaration of Conformity U161 AD EC Declaration of Conformity U163 AA R No 20000h U165 ...
Страница 128: ...Siemens AG Process Industries and Drives Postfach 48 48 90026 NÜRNBERG GERMANY www siemens com drives ...