Mounting and connecting the HMI device
3.1 Preparation for mounting
Comfort Panels
Operating Instructions, 03/2012, A5E03404994-02
33
3.1.5
Preparing the mounting cutout
NOTICE
Stability of the mounting cutout
The material in the area of the mounting cutout must provide sufficient strength to
guarantee the enduring and safe mounting of the HMI device.
The force of the clamps or operation of the device may not lead to deformation of the
material in order to achieve the degrees of protection described below.
Degrees of protection
The degrees of protection of the HMI device can only be guaranteed if the following
requirements are met:
●
Material thickness at the mounting cutout for a protection rating of IP65 or Front face
only Type 4X/Type 12 (indoor use only): 2 mm to 6 mm
●
Permitted deviation from plane at the mounting cutout: ≤ 0.5 mm
This condition must be fulfilled for the mounted HMI device.
●
Permissible surface roughness in the area of the seal: ≤ 120 µm (R
z
120)
Compatibility of the mounting cutout to other HMI devices
The mounting cutouts of the following HMI devices are compatible with the mounting cutouts
of the following predecessor devices:
HMI device
Mounting cutout compatible to
KP400 Comfort
OP 77B
KTP400 Comfort
TP 177B 4"
KP700 Comfort
OP 277 6"
TP700 Comfort
TP 177B 6", MP 177 6", TP 277 6"
KP900 Comfort
MP 277 8" key
KP1500 Comfort
MP 377 12" key
Please note that although the dimensions for the mounting cut-out are the same, the device
depth and/or the enclosure front dimensions may differ from the respective dimensions of the
predecessor devices.
Содержание SIMATIC TP700 Comfort Outdoor
Страница 6: ...Preface Comfort Panels 6 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 12: ...Table of contents Comfort Panels 12 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 24: ...Overview 1 6 Software options Comfort Panels 24 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 28: ...Safety instructions 2 3 Notes about usage Comfort Panels 28 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 136: ...Commissioning the device 4 4 Configuring the device Comfort Panels 136 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 164: ...Operating a project 6 9 Closing the project Comfort Panels 164 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 168: ...Maintenance and care 7 4 Recycling and disposal Comfort Panels 168 Operating Instructions 03 2012 A5E03404994 02 ...