Commissioning the device
4.4 Configuring the device
Comfort Panels
116
Operating Instructions, 03/2012, A5E03404994-02
Procedure
Proceed as follows:
1.
Use "Properties" to open the "MPI" or "PROFIBUS" dialog.
2.
If there are several masters connected on the bus, deactivate the "Panel is the only
master on the bus" check box.
3.
Enter the bus address for the HMI device under "Address".
NOTICE
The bus address in the "Address" text box must be unique throughout the
MPI/PROFIBUS DP network.
4.
Select the transfer speed under "Transmission Rate".
5.
Enter the highest station address on the bus under "Highest Station Address" or "Highest
Station.
6.
PROFIBUS only: Select the desired profile under "Profile".
Use "Bus Parameters" to view the profile data.
NOTICE
The bus parameters must be the same for all stations in the MPI/PROFIBUS DP
network.
7.
Confirm your entries with "OK".
Result
The MPI/PROFIBUS DP settings of the HMI device have been changed.
See also
Configuring the data channel (Page 113)
Reference for functions (Page 79)
Содержание SIMATIC TP700 Comfort Outdoor
Страница 6: ...Preface Comfort Panels 6 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 12: ...Table of contents Comfort Panels 12 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 24: ...Overview 1 6 Software options Comfort Panels 24 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 28: ...Safety instructions 2 3 Notes about usage Comfort Panels 28 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 136: ...Commissioning the device 4 4 Configuring the device Comfort Panels 136 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 164: ...Operating a project 6 9 Closing the project Comfort Panels 164 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 168: ...Maintenance and care 7 4 Recycling and disposal Comfort Panels 168 Operating Instructions 03 2012 A5E03404994 02 ...