General technical specifications
5.2 Standards Compliance
EIP-200S Ethernet/IP Adapter Distributed I/O System
System Manual, 06/2018, A5E44345053-AB
93
FM approval
Factory Mutual Research (FM)
Approval Standard Class Number 3600 and 3611
Approved for use in:
Class I, Division 2, Gas Group A, B, C, D, Temperature Class T4C Ta = 60° C
Class I, Zone 2, IIC, Temperature Class T4 Ta = 60° C
Canadian Class I, Zone 2 Installation per CEC 18-150
IMPORTANT EXCEPTION: See Technical Specifications for the number of inputs or outputs
allowed on simultaneously. Some models are de-rated for Ta = 60° C.
WARNING
Risk of substituion of components
Substitution of components can impair the suitability for Class I, Division 2 and Zone 2.
Repair of units should only be performed by an authorized Siemens Service Center.
ATEX approval
ATEX approval applies to DC models only. ATEX approval does not apply to AC and Relay
models.
EN 60079-0:2006: Explosive Atmospheres - General Requirements
EN 60079-15:2005: Electrical Apparatus for Potentially Explosive Atmospheres;
Type of protection 'nA'
II 3 G Ex nA IIC T4 Gc
IMPORTANT EXCEPTION: See Technical Specifications for the number of inputs or outputs
allowed on simultaneously. Some models are de-rated for Ta = 60° C.
Install modules in a suitable enclosure providing a minimum degree of protection of IP54
according to EN 60529 and take into account the environmental conditions under which the
equipment will be used.
When the temperature under rated conditions exceed 70° C at the cable entry point, or 80° C
at the branching point of the conductors, the temperature specification of the selected cable
should be in compliance with the actual measured temperature.
Provisions should be made to prevent the rated voltage from being exceeded by transient
disturbances of more than 40%.
C-Tick approval
The ET 200S distributed I/O system satisfies requirements of standards to AS/NZS 2064
(Class A).