Product overview
1.2 What is the ET 200S distributed I/O system?
EIP-200S Ethernet/IP Adapter Distributed I/O System
10
System Manual, 06/2018, A5E44345053-AB
Component
Function
Drawing
Electronic module
Is connected to the terminal module and determines
the function:
•
Digital input modules with 24 VDC, 120/230 VAC
and NAMUR
•
Digital output modules with 24 VDC and
120/230 VAC
•
Relay modules
•
Analog input modules with voltage, current, and
resistance measurement; thermal resistance; and
thermocouples
•
Analog output modules for voltage and current
Terminating module
Terminates the ET 200S and can be used to carry 6
reserve fuses (5 mm x 20 mm).
Shield contact
For connecting cable shields.
Slot number labels
For identifying the slots on the terminal module.
Color identification labels
Permit customer and country-specific identification of
the terminals on the terminal module.
Labeling sheet (DI A4, perfo-
rated, foil)
For machine labeling or printing - 80 strips per label-
ing sheet