Commissioning and diagnostics
4.1 Configuring the ET 200S
EIP-200S Ethernet/IP Adapter Distributed I/O System
System Manual, 06/2018, A5E44345053-AB
83
Configuration table in your configuration software and address space
The byte and bit addresses result from the sequence of the grouped modules in User
Configured mode.
Slot
Module
Grouping
I/O address
Inputs
Outputs
1
6ES7138-4CA00-0AA0 PM-E 24 VDC
---
---
---
2
6ES7131-4BB00-0AB0 2DI 24 VDC
Yes
0.0 to 0.1
3
6ES7131-4BB00-0AB0*2DI 24 VDC
0.2 to 0.3
4
6ES7134-4FB00-0AB0 2AI U
No
1 to 4
5
6ES7135-4GB00-0AB0 2AO I
No
0 to 3
6
6ES7131-4BD00-0AA0*4DI 24 VDC
Yes
0.4 to 0.7
7
6ES7132-4BD00-0AA0 4DO 24 VDC
Yes
4.0 to 4.3
8
6ES7132-4BB00-0AB0*2DO 24 VDC
4.4 to 4.5
9
6ES7132-4HB00-0AB0*2DO Rel.
4.6 to 4.7
10
6ES7134-4FB00-0AB0 2AI U
No
5 to 8
11
6ES7135-4GB00-0AB0 2AO I
No
5 to 8
12
6ES7138-4CA00-0AA0 PM-E 24 VDC
---
---
---
13
6ES7132-4BB30-0AB0 2DO 24 VDC
Yes
9.0 to 9.1
14
6ES7132-4BB30-0AB0* 2DO 24 VDC
Yes
9.2 to 9.3
15
6ES7138-4CA00-0AA0 PM-E 230 VAC
---
---
---
16
6ES7132-4BB00-0AB0*2DO 24 VDC/0.5 A
Yes
9.4 to 9.5
17
6ES7132-4BB00-0AB0*2DO 24 VDC/0.5 A
Yes
9.6 to 9.7
18
3RK1903-0BA00 PM-D
---
---
---
19
3RK1301-xxB00-0AA0 DS
Yes
9.0 to 9.3
10.0 to 10.3
20
3RK1301-xxB00-0AA0 *DS
9.4 to 9.7
10.4 to 10.7
21
3RK1301-xxB00-0AA0 DS
Yes
10.0 to 10.3
11.0 to 11.3
No grouping
If you do not want to group the configuration of the ET 200S distributed I/O system digital
input/output modules and motor starters in a single byte, use only those module designations
without " * " in the hardware catalog of your configuration software.
Each electronic module/motor starter will then occupy one byte in the input or output area of
the process image.