EIP-200S Ethernet/IP Adapter
2.2 Parameters for the EIP-200S Ethernet/IP Adapter
EIP-200S Ethernet/IP Adapter Distributed I/O System
20
System Manual, 06/2018, A5E44345053-AB
2.2
Parameters for the EIP-200S Ethernet/IP Adapter
Parameter assignment
Parameters for the EIP-200S Ethernet/IP Adapter are set by using the ZNX-EIP-200S
Configuration Tool software. After loading new parameters into the interface module, the
parameters take effect immediately.
The following table describes the parameters of the interface module:
EIP-200S Ethernet/IP
Adapter IM
Value range
Default
Applicability
Interference frequency suppres-
sion
50 Hz / 60 Hz
60 Hz
ET 200S
Reference junction slot
None / 2 to 63
None
ET 200S
Reference junction
RTD on channel 0 /
RTD on channel 1
RTD on channel 0
ET 200S
Bus length
≤
1 m / > 1 m
≤
1m
ET 200S
Interference frequency suppression
The frequency of your alternating voltage system can affect measured values negatively,
particularly in the case of both measurements in small voltage ranges and thermocouples.
Specify here the dominant line frequency in your system (50 Hz or 60 Hz).
The interference frequency suppression parameter is valid for all analog electronic modules.
The integration time and conversion time of the individual modules are also set by means of
this parameter.
Bus length
The bus length parameter specifies the maximum width of the station backplane bus:
●
≤
1 m: the default setting for the maximum bus length is 1 m.
●
> 1 m: the bus length of the ET 200S system is > 1 m and can be up to 2 m. However,
this setting will increase the response time of the ET 200S.