Planning the RF200 system
4.3 Installation guidelines
SIMATIC RF200
52
System Manual, 07/2017, J31069-D0227-U001-A9-7619
Table 4- 19 Flush-mounting of transponders and readers
Representation
Description
Problem:
Flush-mounting of transponders and
readers is possible in principle.
However, the size of the transmis-
sion window is significantly reduced.
The following measures can be
used to counteract the reduction of
the window:
Remedy:
Enlargement of the non-metallic
spacer below the transponder
and/or reader.
The transponder and/or reader are
10 to 20 mm higher than the metal
surround.
(The value x ≥ 100 mm is valid, for
example, for RF260R. It indicates
that, for a distance x ≥ 100 mm, the
reader can no longer be significantly
affected by metal.)
Remedy:
Increase the distances a, b to metal.
The following rule of thumb can be
used:
•
Increase a, b by a factor of 2 to 3
over the values specified for
metal-free areas
•
Increasing a, b has a greater
effect for readers or transpond-
ers with a large limit distance
than for readers or transponders
with a small limit distance.
Содержание SIMATIC RF200
Страница 12: ...Table of contents SIMATIC RF200 12 System Manual 07 2017 J31069 D0227 U001 A9 7619 ...
Страница 18: ...Safety notes SIMATIC RF200 18 System Manual 07 2017 J31069 D0227 U001 A9 7619 ...
Страница 25: ...System overview 3 2 Overview of transponders SIMATIC RF200 System Manual 07 2017 J31069 D0227 U001 A9 7619 25 ...
Страница 26: ......
Страница 102: ...Planning the RF200 system 4 4 Further information SIMATIC RF200 102 System Manual 07 2017 J31069 D0227 U001 A9 7619 ...
Страница 160: ......