Structure of the CPU 410-5H
3.3 Status and error displays
CPU 410-5H Process Automation
44
System Manual, 09/2014, A5E31622160-AB
LEDs LINK1 OK and LINK2 OK
When commissioning the fault-tolerant system, you can use the LINK1 OK and LINK2 OK
LEDs to check the quality of the connection between the CPUs.
LED LINKx OK
Meaning
Lit
The connection is OK
Flashes
The connection is not reliable, and the signal is disrupted
Check the connectors and cables
Ensure that the fiber-optic cables are installed in accordance with the guidelines in Chapter
Installation of fiber-optic cables (Page 206).
Check whether the synchronization module works in another CPU.
Dark
The connection is interrupted, or there is insufficient light intensity
Check the connectors and cables
Ensure that the fiber-optic cables are installed in accordance with the guidelines in Chapter
Installation of fiber-optic cables (Page 206).
Check whether the synchronization module works in another CPU.
If necessary, replace the synchronization module in the other CPU.
LED MAINT
This LED indicates that maintenance is required. Maintenance is required when there are
problems with the synchronization modules or if maintenance is demanded by one of the
PROFINET devices. For more information, refer to the STEP 7 Online Help.
The LED MAINT also displays an error during address assignment of the PROFINET
interfaces X5 or X8.
Diagnostics buffer
In STEP 7, you can select "PLC -> Module Information" to read the cause of an error from
the diagnostics buffer.