Installation, connecting up, sources of problems
4.3 Possible sources of problems and how to deal with them
SCALANCE X-100
50
Operating Instructions, 04, A2B00060666D
4.3
Possible sources of problems and how to deal with them
Fuses
Note
Some of the Industrial Ethernet switches of the SCALANCE X-100 product line have a
resettable fuse / PTC. If the fuse triggers (all LEDs are off despite correctly applied power
supply), the device should be disconnected from the power supply for approximately 30
minutes before turning it on again.
Link display on the optical ports
The Industrial Ethernet switches SCALANCE X104-2, SCALANCE X106-1 and
SCALANCE X112-2 support "far-end fault" on the optical ports but do not use this for the
corresponding link display. This means that if there is only a cable connected in the receive
direction on the optical port, a far-end fault is detected and no data is forwarded. The Link
LED is already lit.
LED display when voltage drops
If both of the power supplies drop below approximately 14 V, this reduced voltage is
indicated by the red fault LED. The L LEDs go off.
If a fault develops, please send the device to your SIEMENS service center for repair.
Repairs on-site are not possible.
Содержание SIMATIC NET SCALANCE X-100 Series
Страница 40: ...Product properties 3 12 Displays SCALANCE X 100 40 Operating Instructions 04 A2B00060666D ...
Страница 54: ...Approvals and markings SCALANCE X 100 54 Operating Instructions 04 A2B00060666D ...
Страница 60: ...Technical specifications 6 1 Technical specifications SCALANCE X 100 60 Operating Instructions 04 A2B00060666D ...
Страница 62: ...References SCALANCE X 100 62 Operating Instructions 04 A2B00060666D ...
Страница 68: ...Dimension drawings 8 1 Dimension Drawing SCALANCE X 100 68 Operating Instructions 04 A2B00060666D ...
Страница 72: ...Glossary SCALANCE X 100 72 Operating Instructions 04 A2B00060666D ...
Страница 74: ...Index SCALANCE X 100 74 Operating Instructions 04 A2B00060666D U UL approval 6 ...