11
IE/AS
−
INTERFACE LINK PN IO
as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000
−
G8976
−
C216
−
03
1 Technical Description, Installation Guidelines,
Operation
This chapter...
This chapter will familiarize you with the performance characteristics, basic
functions and installation of the IE/AS-INTERFACE LINK PN IO master module.
You will learn the following:
S
How to install the IE/AS-i LINK
S
Which display and control elements the IE/AS-i LINK provides.
1.1
General Notes on Operation − Safety Warnings
!
Warning
WARNING
−
EXPLOSION HAZARD: DO NOT DISCONNECT EQUIPMENT
WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT.
!
Warning
When used under hazardous conditions (zone 2), devices of the
IE/AS-INTERFACE LINK PN IO product line must be installed in an enclosure.
To comply with ATEX95 (previously ATEX100a) EN 60079-15, this enclosure must
meet the requirements of at least IP54 in compliance with EN 60529.
!
Warning
When used under hazardous conditions:
S
If the temperature of the cable or wiring entry point exceeds 70
°
C or the
temperature of the connecting terminal on the IE/AS-i LINK exceeds 80
°
C,
special precautions must be taken:
If the IE/AS-i LINK is operated at ambient temperatures 50
°
C to 60
°
C, only
cables with a maximum permitted temperature of at least 80
°
C may be used.
S
Provisions shall be made to prevent the rated voltage from being exceeded by
transient disturbances of more than 40%.
This criterion is fulfilled, if supplies are derived from SELV (Safety Extra Low
Voltage), only.
S
The IE/AS-i LINK is intended only for vertical installation.