6 Configuring with STEP 7 or a GSDML File
103
IE/AS
−
INTERFACE LINK PN IO
as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000
−
G8976
−
C216
−
03
Configuring the PROFINET IO properties of the Ethernet Interface
This function is available on the IE/AS-i LINK as of firmware version V2.0.
If you double-click on row 2 in the configuration table (AS-i addr.: “
X1
”), you open
the dialog for the PROFINET IO properties of the IE/AS-i LINK. Here, you can set
the following parameters:
S
“General” Tab
−
Display of the essential master data of the module
−
Setting of the name for the PROFINET IO properties of the Ethernet
interface
−
Entering a comment
S
“Addresses” tab
Setting of the diagnostic address for the PROFINET IO communication of the
IE/AS-i LINK
S
“IO Cycle” tab
−
Setting the update time for the IP cycle
−
Setting the number of update cycles with missing I/O data
Configuring ports “Port 1” and “Port 2”
This function is available on the IE/AS-i LINK as of firmware version V2.0.
When you double-click on row 3 or row 4 (AS-i addr.: “
X1P1
” or “
X1P2
”) in the
configuration table opens the properties dialog of Port 1 or Port 2 of the LAN
interface of the IE/AS-i LINK. You can set the following parameters for the relevant
port:
S
“General” Tab
−
Setting the port name
−
Entering a comment
S
“Addresses” tab
Setting the diagnostic address of the port
S
“Topology” tab
Here, you can interconnect the selected port of the IE/AS-i LINK with the port of
another device in the IO system.
−
The “Local port” shows the selected port of the IE/AS-i LINK.
−
In the “Remote port” drop-down list box, you can select the required port
from the devices available in the IO system.
−
The “Medium” box displays the connection.
The “cable name” cannot be selected for copper.
The “line data” box is only available for devices with IRT capability.