Assembling and Installing Systems
A-14
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
Handling the Shields
Observe the following points with regard to the shield:
•
Only use cable clamps made of metal to secure braided shields. The clamps
must surround the shield over a large area and provide good contact.
•
Connect the shield to a shield bus immediately after entry of the cable into the
cabinet. Route the shield to the module but do not connect it there again to the
chassis ground or the shield bus.
•
For installation other than in cabinets (for example, wall mounting), you can
provide contact between the cable shields and the cable duct.
Shown in the figure A-4 are some methods of securing shielded cables with cable
clamps.
Figure A-4
Mounting Cable Shields
Содержание Simatic M7-400
Страница 10: ...Preface x S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 20: ...Contents xx S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 66: ...Installing the S7 400 2 40 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 74: ...Addressing the S7 400 3 8 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 118: ......
Страница 170: ...Starting Up 6 20 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 194: ...Maintenance 7 24 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 252: ...Assembling the M7 400 8 58 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 310: ...Glossary Glossary 18 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 316: ...Index Index 6 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...