Networking
5-4
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
Number of Nodes
MPI
PROFIBUS DP
127
127 *
(default: 32)
of which:
1 master (reserved)
1 PG port (reserved)
1 PG port (reserved)
125 slaves or other masters
*
Observe the CPU-related maximum numbers in the Reference Manual CPU Data,
Chapter 4
MPI/PROFIBUS-DP Addresses
In order for all nodes to be able to communicate with one another, you must assign
them an address:
•
In the MPI network, an MPI address
•
A PROFIBUS-DP address in the PROFIBUS-DP network
Default MPI Addresses
The following table shows the default MPI address and the max. MPI address with
which the devices are shipped:
Node (Device)
Default MPI Address
Default Highest MPI
Address
Programming device
0
32
OP
1
32
CPU
2
32
Note
If you change the parameter assignment of the highest MPI address of the MPI/DP
interface, the new address remains set even after memory reset, voltage failure or
removing/inserting the CPU.
Rules for MPI Addresses
Observe the following rules before assigning MPI addresses:
•
All MPI addresses in an MPI network must be different.
•
The highest possible MPI address must be
the highest actual MPI address
and must be set to the same value for all nodes. (Exception: connecting a
programming device to two or more nodes.)
Содержание Simatic M7-400
Страница 10: ...Preface x S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 20: ...Contents xx S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 66: ...Installing the S7 400 2 40 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 74: ...Addressing the S7 400 3 8 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 118: ......
Страница 170: ...Starting Up 6 20 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 194: ...Maintenance 7 24 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 252: ...Assembling the M7 400 8 58 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 310: ...Glossary Glossary 18 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 316: ...Index Index 6 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...