Installing the S7-400
2-15
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
The figure below shows how much space you must allow for when assembling an
S7-400 from two racks with a cable duct or fan subassembly. This requirement is
increased by a height of 400 mm for each additional rack with a cable duct or fan
subassembly.
Mounting depth, fitted: max. 237 mm
840 mm
19-inch reference level
Cable duct/fan subassembly
Cable duct/fan subassembly
1
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5
6 7 8 9 10 11 12 13 14 15 16 17 18
Note
A minimum clearance as shown in the above figure between rack and cable duct
or fan subassembly must not be provided, but is essential between two adjacent
racks and between racks and other equipment.
Содержание Simatic M7-400
Страница 10: ...Preface x S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 20: ...Contents xx S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 66: ...Installing the S7 400 2 40 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 74: ...Addressing the S7 400 3 8 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 118: ......
Страница 170: ...Starting Up 6 20 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 194: ...Maintenance 7 24 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 252: ...Assembling the M7 400 8 58 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 310: ...Glossary Glossary 18 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 316: ...Index Index 6 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...