Installing the S7-400
2-11
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
Space Required When Using Cable Channels and Fan Subassemblies
A cable duct or fan subassembly must be installed in the 19-inch pitch immediately
below the rack. Additional space for cable routing must be provided on both sides.
The following figure shows how much space you need to allow for when using a
cable duct or fan subassembly.
Cable duct/fan subassembly
440 mm
Mounting depth, fitted: max. 237 mm
522.5 mm (with cable duct)
19-inch reference level
542.5 mm (with fan subassembly)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Dimensions of the Racks
The following figure shows the dimensions for racks with 18, 9 and 4 slots and the
positions of cutouts for screw mounting.
The cutouts are arranged according to the 19-inch standard.
Содержание Simatic M7-400
Страница 10: ...Preface x S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 20: ...Contents xx S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 66: ...Installing the S7 400 2 40 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 74: ...Addressing the S7 400 3 8 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 118: ......
Страница 170: ...Starting Up 6 20 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 194: ...Maintenance 7 24 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 252: ...Assembling the M7 400 8 58 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 310: ...Glossary Glossary 18 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 316: ...Index Index 6 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...