5. Delete your own and imported server data.
6. Close the project.
7. Delete the DCF file in project directory (typically ProjectName.dcf).
8. Reopen the project in the configuration mode.
9. Create your own server data, making sure to maintain the original symbolic computer name
(server prefix) (see step 2).
10.Import all imported packages again (see step 3).
11.Reconfigure the preferred server and default server (see step 4).
12.Close the project.
CPU load
If data, transferred from a server to a client, cannot be processed at the same speed, the client
rejects the data frames from a specified threshold value.
The following process control messages are issued in conjunction with this:
● 1000200: "WCCRT:Status"
You will find the following additional information in the comment of this message or in the log
file "WinCC_Sys_<x>.log":
● 1000200,4,,<Computer name>, DataManager Runtime, RPC call took longer than 5000
msec
(Client requires a very long time to process the data)
● 1000200,4,,<Computer name>, DataManager Runtime, Update data for Client '<client
name>' lost,
(message frames for the client are discarded on the server)
Data may be lost on the client.
See also
Internet: WinCC demo projects (
https://support.industry.siemens.com/cs/products?
search=demo&dtp=ExampleOfUse&o=DefaultRankingDesc&pnid=14866&lc=en-WW
)
http://support.automation.siemens.com/WW/view/de/109482515 (
support.automation.siemens.com/WW/view/en/109482515
)
WinCC Release Notes
2.3 Notes on WinCC
WinCC: General information and installation
72
System Manual, 02/2017, A5E40840020-AA