Programming
5.6 Diagnostic function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
52
Manual, 06/2019, A5E46959434-AA
5.6
Diagnostic function blocks
Diagnostic function blocks are used for querying the status information of all the DALI
devices.
5.6.1
DALI_DEV_GTIN
Description
DALI_DEV_GTIN is used for querying the GTIN (Global Trade Item Number) of device (refer
to data flow path 6 (Page 23)).
Parameter
The following table shows the parameters of the function block:
Parameter Declaration Data type Memory
area
Description
READ
Input
BOOL
I, Q, M, D,
L or Con-
stant
Query the GTIN of device upon a rising edge.
DEV_TYP
E
USInt
I, Q, M, D,
L or Con-
stant
Select the device type:
•
1: Control gear
•
2: Input device (Sensor)
ADDRES
S
USInt
I, Q, M, D,
L or Con-
stant
Specify the short address of the device.
Range: 0 to 63
CM_DALI InOut
"DALI_CT
RL"
The data block of DALI_CTRL specifies the CM 1xDALI which com-
municates with the current function block.
BUSY
Output
BOOL
I, Q, M, D,
L
Status parameter:
•
BUSY = 0: Processing of job is terminated.
•
BUSY = 1: Job is still being committed.
ACTIVE
BOOL
I, Q, M, D,
L
Status parameter:
•
ACTIVE = 0: Job is not yet started.
•
ACTIVE = 1: Job is being executed.
DONE
BOOL
I, Q, M, D,
L
Status parameter:
•
DONE = 0: Job is not yet started or still executing.
•
DONE = 1: Job is executed without errors.