Programming
5.5 Control gear dimming function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
51
Parameter
The following table shows the parameters of the function block:
Parameter Declaration Data type Memory
area
Description
GOTO
Input
BOOL
I, Q, M, D,
L or Con-
stant
Go to the specified scene upon a rising edge.
GROUP
BOOL
I, Q, M, D,
L or Con-
stant
Specify the short address or group address of the control gear:
•
GROUP = 0: ADDRESS indicates the short address or broadcast.
•
GROUP = 1: ADDRESS indicates the group address.
ADDRES
S
USint
I, Q, M, D,
L or Con-
stant
Identify the address information of the CM 1xDALI.
When GROUP = 0, ADDRESS
indicates the short address or
broadcast:
•
0 to 63: Specify the short
address of the device
•
253: Broadcast the un-
addressed devices
•
255: Broadcast all the devices
When GROUP = 1, ADDRESS
indicates the group address:
•
0 to 15: Group address
SCENE_N
UM
USint
I, Q, M, D,
L or Con-
stant
Go to the specified scene.
Range: Less than 16
CM_DALI InOut
"DALI_CT
RL"
The data block of DALI_CTRL specifies the CM 1xDALI which com-
municates with the current function block.
BUSY
Output
BOOL
I, Q, M, D,
L
Status parameter:
•
BUSY = 0: Processing of job is terminated.
•
BUSY = 1: Job is still being committed.
ACTIVE
BOOL
I, Q, M, D,
L
Status parameter:
•
ACTIVE = 0: Job is not yet started.
•
ACTIVE = 1: Job is being executed.
DONE
BOOL
I, Q, M, D,
L
Status parameter:
•
DONE = 0: Job is not yet started or still executing.
•
DONE = 1: Job is executed without errors.
ERROR
BOOL
I, Q, M, D,
L
Status parameter:
•
ERROR = 0: No error occurs.
•
ERROR = 1: Error occurs during processing.
STATUS
BYTE
I, Q, M, D,
L
When ERROR = 0, STATUS has
following three values:
•
16#00: Idle
•
16#01: Executing
•
16#7F: Completed
When ERROR = 1, STATUS
shows the detailed error code. For
the detailed meaning of each
error code, refer to Parameter