Technical data
Bus protocol
PROFINET IO
•
IRT with the option "high flexibility"
•
IRT with the option "high performance"
Supported Ethernet services
PROFINET IO (Device)
•
ping
•
arp
•
LLDP
•
Network diagnostics (SNMP)
•
DCP
•
Prioritized startup
•
Media redundancy
PROFINET interface
•
Connection socket
2 x M12 d-coded
•
Switch function
Yes, internal
•
Auto-crossover
Yes, if autonegotiation is enabled
Manufacturer ID (Vendor ID)
002A
H
Device ID (DeviceID)
0306
H
Voltages and currents
Supply voltage 1L+
DC 24 V
•
Reverse polarity protection
Yes, against destruction, loads are activated
•
Infeed current 1L+
Max. 4 A
Supply voltage 2L+
DC 24 V
•
Reverse polarity protection
Yes, against destruction, loads are activated
•
Infeed current 2L+
Max. 4 A
Current consumption
From supply voltage (1L+)
Typ. 100 mA (no digital output activated)
From supply voltage (2L+)
Typ. 5 mA (no digital output activated)
Power loss of the device
type 4.5 W (if all channels are set as digital input)
type 6.5 W (if all channels are set as digital output)
Total current of the outputs
•
All mounting positions to 60°C
Max. 3.9 A per 1L+ and 2L+
Digital inputs/digital outputs
Number of configurable inputs/outputs
8
Number of inputs that can be controlled simultan
eously
8, in all mounting positions
Insulation
Insulation test voltage
•
Ethernet interface
1500 V
rms
(IEEE802.3, Type Test)
•
All other circuit elements
707 V DC (type test)
Electrical isolation
•
Between 1L+ and 2L+
Yes
146
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
I/O device digital inputs/digital outputs
9.3 I/O device digital inputs/digital outputs