Configuring the IO-Link Master with GSD fileGSD
1. Install the GSD file in HW Config. The GSD file is available on the Internet
https://support.industry.siemens.com/cs/ww/en/view/33291771
).
2. Select the IO-Link Master I/O device in the hardware catalog of
HW Config.
3. You can freely choose the address space in the
Properties > Addresses
field for each slot
of the IO-Link Master. In contrast to HSP configuration, the address space on Slot 1 "4 IO-L"
is set permanently to 32 byte inputs and outputs. Additional information on possible
configurations is available in the chapter I/O address space (Page 251).
4. Assign the IO-Link Master parameters. You can assign the parameters separately for each
functional unit:
– The PROFINET IO parameters are accessed by double-clicking Slot 0.
– The IO-Link parameters are accessed by double-clicking Slot 1.
– The 8 digital input and 4 digital output parameters are accessed by double-clicking Slot
2.
Configuring the IO‑Link device via S7‑PCTS7-PCT
1. Select Slot 1 "4 IO-L" from the configuration table of the I/O device IO-Link Master.
2. Right-click and select "Start Device Tool" in the following shortcut menu.
Result: S7-PCT is started.
3. Now start with the parameter assignment of the IO-Link Devices, sensors, and actuators.
You can find additional information in the S7-PCT online help.
Response of the IO-Link Master in unparameterized state and after "Resetting the IO-Link
settings" via S7-PCT
• All ports of the IO-Link Master are deactivated.
• All user data are equal to 0.
• All bits of the value status are set to "invalid."
• The maintenance data 1 to 3 are deleted.
4.2.2
Configuring the IO-Link Master 6ES7148-6JD00-0AB0
Introduction
The IO-Link Master 6ES7148-6JD00-0AB0 is configured and parameters are assigned in the
user interface of the selected configuration software.
"
Configuring
" is understood to mean arranging, setting and networking of devices and
modules.
"
Assigning parameters
" is understood to mean setting the properties of the components
used. The parameters of the hardware and the settings for the data exchange are assigned in
the process.
65
Configuring
4.2 Configuring an IO-Link master
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Содержание SIMATIC ET 200eco PN
Страница 233: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 234 Dimensional drawings C ...
Страница 265: ...266 ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN Open Source Software ...
Страница 278: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 279 Y Y cable 37 Index ...