Technical specifications
•
between 1L+ and 2L+
Yes
•
between 1L+, channels and all other switching
parts
No
•
Between channels
No
•
between Ethernet and all other switching parts Yes
Status, interrupts, diagnostics
Interrupts
Yes
•
Hardware interrupt (device notification)
Yes
Diagnostics function
Yes
•
Group error/maintenance
Yes; red/yellow LED "SF/MT"
•
Bus monitoring PROFINET IO
Red "BF" LED
•
Monitoring of supply voltage 1L+
Green "ON" LED
•
Monitoring of supply voltage 2L+
Green "24 V DC" LED
•
Existing connection to network
Green "P1 LK" and "P2 LK" LED for PROFINET IO
infeed and loop-through
•
IO-Link port
– Port in IO-Link mode
– Port in SIO mode
green/red LED "IO-L"
Green LED "Q"
•
Diagnostic information can be read
Yes
Monitoring for
•
Missing 2L+
Yes
•
Sensor supply short-circuit
Yes; device supply to ground
Sensor supply
Number of outputs
4
Load current
500 mA per output
Short-circuit protection
Yes, electronic
IO-Link port
Number of ports
4
Number of ports that can be controlled simultan
eously
4, in all mounting positions
IO-Link protocol 1.0
Yes
IO-Link protocol 1.1
Yes
Transmission rate
4.8 kBaud (COM1), 38.4 kBaud (COM2), 230.4
kBaud (COM3)
Size of the process data, input per port
32 bytes + 1 byte PQI
Size of the process data, input per module
128 bytes + 4 bytes PQI
Size of the process data, output per port
32 bytes
Size of the process data, output per module
128 bytes
Memory size for device parameters
2 Kbytes; for each port
Master backup
possible; with function block LIOLink_Master
212
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
IO-Link Master
11.2 IO-Link Master (6ES7148-6JD00-0AB0)
Содержание SIMATIC ET 200eco PN
Страница 233: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 234 Dimensional drawings C ...
Страница 265: ...266 ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN Open Source Software ...
Страница 278: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 279 Y Y cable 37 Index ...