Technical data
Insulation test voltage
•
Ethernet interface
1500 V
rms
(IEEE802.3, Type Test)
•
All other circuit elements
707 V DC (type test)
Electrical isolation
•
Between 1L+ and 2L+
Yes
•
Between 1L+, channels and all other circuit ele
ments
No
•
Between channels
No
•
Between Ethernet and all other circuit elements Yes
Status, interrupts, diagnostics
Interrupts
Yes
Diagnostics function
Yes
•
Group error/maintenance
Red/yellow "SF/MT" LED
•
Bus monitoring PROFINET IO
Red "BF" LED
•
Monitoring of supply voltage 1L+
Green "ON" LED
•
Existing connection to network
Green "P1 LK" and "P2 LK" LED; LED for PROFINET IO
infeed and loop-through
•
Digital input
Green LED
•
Fault at digital input
Red LED
•
Diagnostic information can be read
Yes
Monitoring for
•
Short-circuit
Yes, per channel group
•
Wire break
Input current < 0.3 mA, per channel
•
Missing sensor supply
Yes
Sensor supply
Number of sensor supplies
8
Load current
100 mA per output
Short-circuit protection
Yes, electronic
Sensor selection data
Cable length, shielded
Max. 30 m
Cable length, unshielded
Max. 30 m
Input voltage
•
Nominal value
DC 24 V
•
For signal "1"
11 to 30 V
•
For signal "0"
-3 to +5 V
Input current
•
At signal "1"
Typ. 7 mA
Input delay
120
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
I/O device digital inputs/digital outputs
9.1 I/O device digital inputs