6-8
Communications Processor CP 541
EWA 4NEB 812 6188-02
Table 6-4
DB1 Error Codes, continued
Error Code
Remedy
Meaning
In DL
Remedy
Meaning
In DR
41
H
XX
H
1
The transmission rate (BDR)
chosen is too low.
Lowest permissible transmission rate is 93.75
Kbps. Enter the right value.
42
H
XX
H
1
The own station number is en-
tered in PRI.
Delete the own station number (value of TLN)
from the priority list (PRI).
43
H
XX
H
1
The station number is duplicated.
Delete the excessive TLN parameter.
44
H
XX
H
1
The priority list has more than
60 entries.
You may make up to 60 entries in the priority
list. Delete the excessive entries.
45
H
XX
H
1
PRI is duplicated.
46
H
XX
H
1
UPDL is duplicated.
47
H
XX
H
1
BSAP is duplicated.
48
H
XX
H
1
L1M is duplicated.
Delete the excessive parameter
49
H
XX
H
1
POL is duplicated.
Delete the excessive parameter.
50
H
XX
H
1
NWI is duplicated.
51
H
XX
H
1
NWO is duplicated.
52
H
XX
H
1
DPWD is duplicated.
53
H
XX
H
1
DPS is present and L1M
0.
Assign the value 0 to parameter L1M.
54
H
XX
H
1
NWI and NWO are 0.
For a DP connection, you must assign a
value
0 to at least one of parameters NWI and
NWO.
55
H
XX
H
1
DP connection configured but 0
is not entered in the user-defined
PRI list.
Enter the value 0 in the user-defined PRI list.
56
H
XX
H
1
STBS and STBR not allowed.
Delete parameters STBS and STBR.
57
H
XX
H
1
L1M is identical to TLN.
Specify the right station number.
58
H
XX
H
SL2 block designator missing.
Specify the SL2 block.
Or carry out a reset.
60
H
FF
H
DB1 is too long.
DB1 may have only 1 Kbyte. Delete all unnec-
essary entries.
1
DR specifies the error location for most error messages. The following error locations are possible:
–
04
H
: error in SL2 block
–
14
H
: error in COM block
–
15
H
: error in DPS block
Diagnostics and Error Handling