H-16
Communications Processor CP 541
EWA 4NEB 812 6188-02
Given in the following are the data blocks (DBs), function blocks (FBs) and
organization blocks (OBs) for station 12 (S5-115F).
DB1 in CP 541
DB1
0:
KS =’DB1 SL2: TLN 12 STQ AKT ’;
12:
KS =’ BDR 500 HSQ 30 ’;
24:
KS =’ TRT 30000 ’;
36:
KS =’ SET 80 ST 1000 ’;
48:
KS =’ SDT 1 80 SDT 2 360 ;’;
60:
KS =’#DPS: NWO 16 NWI 16 ’;
72:
KS =’ DPWD 50 ;#’;
84:
KS =’#COM: L1F 0 POL 10 ’;
96:
KS =’ BSAP 52 UPDL 10 ’;
108:
KS =’ PRI ......... ;#’;
120:
KS =’ END ’;
132:
Parameter assignment with COM 115F
Parameters for operating system
0 means not used
User EPROM capacity
(0/8/16/32):
16 KBytes
Max. PLC cycle duration^
(10..16383): 25 * 10ms
Time of occurrence of second error
(1..255): 9 * 10min
Calculated test frame time
: 51 s
Test cycle time
(1..255):
9 * 10min
User time update :
max. interval (2..16383):10 * 10ms
Interrupt processing: max. interval (2..255):5 * 10ms
Interval for OB 13 (0;10..16383):
80 * 10ms
Short discrepancy time, no interrupt DI
(1..63): 3 * 10ms
Short discrepancy time, interrupt DI
(0;1..255): 20 ms
Short discrepancy time, analog input
(0;2..63): 0 * 10ms
I/O per. error tolerance variant
(1..4): 1
DB no. for long discrepancy times
(0;4..255): 4
Min. absolute AI deviation
(0;16..255): 16
Global lower wire-break limit
(norm. KF): 0
Global upper wire-break limit
(norm. KF): 0
Station 12
DB1 in CP 541
S5-115F with
COM 115F
Program Examples