H-9
Communications Processor CP 541
EWA 4NEB 812 6188-02
Given in the following are the data blocks (DBs), functions blocks (FBs) and
organization blocks (OBs) for the slave (CP 541 with S5-90U). In the
S5-90U, you must define data block DB 10 with 50 data words in addition to
the following data.
DB1 in CP 541
DB1
0:
KS =’DB1 SL2: TLN 3 STQ AKT ’;
12:
KS =’ BDR 500 HSQ 30 ’;
24:
KS =’ TRT 30000 ’;
36:
KS =’ SET 80 ST 1000 ’;
48:
KS =’ SDT 1 80 SDT 2 360 ;’;
60:
KS =’ DPS: NWO 2 NWI 5 ’;
72:
KS =’ DPWD 50 ;’;
84:
KS =’#COM: L1F 0 POL 10 ’;
96:
KS =’ BSAP 52 UPDL 10 ’;
108:
KS =’ PRI ......... ;#’;
120:
KS =’ END ’;
132:
DB1 in S5-90U PLC
DB1
0:
KS =’DB1 SL1: SLN 3 ’;
12:
KS =’ EF DB10DW0 CBR FY6 ’;
24:
KS =’ SF DB10DW33 CBS FY8 ;’;
36:
KS =’ END ’;
48:
DP Slave
DB1 in CP 541
DB1 in S5-90U
Program Examples