3-3
Communications Processor CP 541
EWA 4NEB 812 6188-02
3.2
Connecting the CP 541
Connect the CP 541 as follows.
We recommend the use of a SITOP power supply unit. If you do not use a
SITOP power supply unit, you must use a safety-separated power supply
meeting the requirements given in Appendix A.
Connect the supply of power (24 VDC) to the three screw terminals on the
CP 541. Ensure correct polarity.
Connect the CP 541 and the programmable controller with the preassembled
connecting cable (see Table 3-1).
Observe correct connector assignments.
Table 3-1
Cable for Connecting the PLC and the CP 541
Length
Order No.
1 m
6ES5 735-8BB00
2.5 m
6ES5 735-8BC50
You connect a programmer (PG) for parameter assignment or to evaluate the
diagnostics block, instead of the programmable controller, to the PG/PLC
connector of the CP 541.
Connect SINEC L2 to the 9-pin subminiature D female connector of the CP
541. Use standard components of SINEC L2 (see the manual: SINEC
L2/L2FO Network Components, 6GK1 970-5CA00-0AA).
The components for SINEC L2 are given in Table 3-2.
Table 3-2
Components for SINEC L2
Name
Order No.
Bus cable
Indoor
6XV1 830-0AH10
For burying in ground
6XV1 830-3AH10
Bus connector IP20
6ES5 762-2AA12
Introduction
Supply of Power
Connecting the
PLC to the CP 541
Connecting the
Programmer
Connecting
SINEC L2
Components for
SINEC L2
Installing and Connecting the CP 541