5-7
Communications Processor CP 541
EWA 4NEB 812 6188-02
5.2.2
Configuring a Non-Safety-Related PLC-PLC Connection
You need this chapter to set up a non-safety-related PLC-PLC connection
from an S5-115F.
You install the non-safety-related PLC-PLC connection with the S5-95F as
shown in Section 4.1.
You assign parameters for the non-safety-related PLC-PLC connection via
the CP 541 as shown in the following table.
Step
Action
Remark
1
Load DB1 into the programmer.
–
2
Enter the station number of the CP 541 with
parameter TLN in frame SL2.
The station number of the CP 541 must be
identical to the node address of the con-
nected PLC.
3
Remove the comment parentheses from the
COM block.
For the change in the COM block to be ef-
fective, you must remove the comment pa-
rentheses.
4
Use parameter L1M to enter the station num-
ber of the L2 station for which the non-safe-
ty-related connection is to be installed.
The S5-115F can only set up a non-safety-re-
lated connection for node address 0 (SINEC
L1 master). This address is reserved in
SINEC L2.
The CP 541 will convert the address to the
station number specified with parameter
L1M.
5
Clear parameter PRI and dummy characters
“...” or enter the priority list.
The CP 541 cannot start with the dummy
characters for the priority list in DB1.
6
Write the modified DB1 into the CP 541.
–
7
Switch the CP 541 to RUN.
Only upon transition from STOP to RUN
will the modified DB1 be stored in the EE-
PROM of the CP 541.
You must observe the following points in the connected PLC:
The station number set in the CP 541 must be identical to the node ad-
dress of the connected programmable controller.
The non-safety-related PLC-PLC connection can contain up to 64 bytes of
data.
Introduction
Assigning Parame-
ters to the CP 541
In the
Programmable
Controller
CP 541 with S5-95F/S5-115F