Technical Specifications
A-17
C7-635 Control System
Status, Interrupts, Diagnostics
Interrupts
•
No interrupts when operated as standard I/O
•
When using the technological functions,
see
CPU 31xC Technological Functions
manual
Diagnostic functions
•
No diagnostics when operated as standard I/O
•
When using the technological functions,
see
CPU 31xC Technological Functions
manual
Data for Selecting an Actuator for Standard DO
Output voltage
•
for signal ”1”
Minimum L+ (–0.8 V)
Output current
•
for signal “1”
Rated value
0.5 A
Permissible range
5 mA to 0.6 A
•
for signal “0” (residual
current)
Maximum 0.5 mA
Load impedance range
48
Ω
to 4 k
Ω
Lamp load
Maximum 5 W
Parallel connection of 2 outputs
•
For redundant load control
Possible
•
For performance increase
Not possible
Triggering of a digital input
Possible
Switching frequency
•
For resistive load
Maximum 100 Hz
•
For inductive load according
to IEC 947-5, DC13
Maximum 0.5 Hz
•
For lamp load
Maximum 100 Hz
•
Fast outputs with resistive
load
Maximum 2.5 kHz
Inductive breaking voltage limited
internally to
(L+) – 48 V, typically
Short-circuit protected output
Yes, electronic
•
Response threshold
1 A, typically
Содержание SIMATIC C7-635
Страница 12: ...Document Guide 1 2 C7 635 Control System A5E00155581 04 ...
Страница 14: ...Product Overview 2 2 C7 635 Control System A5E00155581 04 Figure 2 2 C7 635 Key ...
Страница 48: ...Installing and Wiring the C7 635 3 26 C7 635 Control System A5E00155581 04 ...
Страница 58: ...Special Features of the C7 635 4 10 C7 635 Control System A5E00155581 04 ...