Technical Specifications
A-22
C7-635 Control System
A5E00155581-04
Status, Interrupts, Diagnostics
Interrupts
•
No interrupts when operated as standard I/O
•
When using the technological functions,
see
CPU 31xC Technological Functions
manual
Diagnostic functions
•
No diagnostics when operated as standard I/O
•
When using the technological functions,
see
CPU 31xC Technological Functions
manual
Actuator Selection Data
Output range (rated values)
•
Voltage
+/– 10 V
0 V to 10 V
•
Current
+/– 20 mA
0 mA to 20 mA
4 mA to 20 mA
Load resistance
(in the rated range of the output)
•
Voltage outputs
– ohmic load
Minimum 1 k
Ω
– capacitive load
Maximum 0.1
μ
F
•
Current outputs
– ohmic load
Maximum 300
Ω
– inductive load
Max. 0.1 mH
Voltage output
•
Short-circuit protection
Yes
•
Short-circuit current
55 mA, typically
Current output
•
No-load voltage
17 V, typically
Destruction limit for externally applied voltages/currents
Output voltage to M
ANA
Maximum 16 V continuous;
•
Current
Maximum 50 mA continuous;
Connection of actuators
•
For voltage output
2-wire connection
Possible, without cable resistance compensation
4-wire connection (measuring
line)
Not possible
•
For current output
2-wire connection
Possible
Содержание SIMATIC C7-635
Страница 12: ...Document Guide 1 2 C7 635 Control System A5E00155581 04 ...
Страница 14: ...Product Overview 2 2 C7 635 Control System A5E00155581 04 Figure 2 2 C7 635 Key ...
Страница 48: ...Installing and Wiring the C7 635 3 26 C7 635 Control System A5E00155581 04 ...
Страница 58: ...Special Features of the C7 635 4 10 C7 635 Control System A5E00155581 04 ...