Technical Specifications
A-8
C7-635 Control System
A5E00155581-04
Data Areas and their Retentive Characteristics
Total retentive data area
(including memory bits; timers;
counters)
All
Bit memories
256 bytes
•
Retentivity
Adjustable
•
Retentivity preset
MB 0 to MB 15
Clock memories
8 (1 memory byte)
Data blocks
Maximum 511
•
Size
Maximum 16 Kbytes
Local data per priority class
Maximum 510 bytes
Blocks
Total
1024 (DBs, FCs, FBs, OBs, SDBs)
The maximum number of blocks that can be loaded is depending on
the MMC used.
OBs
See instruction list
Size
Maximum 16 Kbytes
Nesting depth
•
Per priority class
8
•
Additional nesting depths
within an error OB
4
FBs
Maximum 512 (FB 0 to FB 511)
•
Size
Maximum 16 Kbytes
FCs
Maximum 512 (FC 0 to FC 511)
•
Size
Maximum 16 Kbytes
Address Areas (I/O)
I/O address area overall
Maximum 1024 bytes/1024 bytes (can be addressed by user)
•
Distributed
Maximum 1,000 bytes
I/O process image
128 bytes/128 bytes
Digital channels
Maximum 8,192
•
Of total, number of local
channels
Maximum 992
•
Integrated channels
24 DI / 16 DO
Analog channels
Maximum 512
•
Of total, number of local
channels
Maximum 248
•
Integrated channels
4 + 1 AI/2 AO
Содержание SIMATIC C7-635
Страница 12: ...Document Guide 1 2 C7 635 Control System A5E00155581 04 ...
Страница 14: ...Product Overview 2 2 C7 635 Control System A5E00155581 04 Figure 2 2 C7 635 Key ...
Страница 48: ...Installing and Wiring the C7 635 3 26 C7 635 Control System A5E00155581 04 ...
Страница 58: ...Special Features of the C7 635 4 10 C7 635 Control System A5E00155581 04 ...