Technical Specifications
A-20
C7-635 Control System
A5E00155581-04
Encoder Selection Data
Input ranges (rated value)/input resistance
•
Voltage
+/– 10 V/100 k
Ω
0 V to 10 V/100 k
Ω
•
Current
+/– 20 mA/50
Ω
0 mA to 20 mA/50
Ω
4 mA to 20 mA/50
Ω
•
Resistance
0
Ω
to 600
Ω
/10 M
Ω
•
Resistive thermometer
Pt 100/10 M
Ω
Permissible input voltage (destruction limit)
•
For voltage input
Maximum 30 V continuous;
•
For current input
Maximum 2.5 V continuous, maximum 24 V transient
Permissible input current (destruction limit)
•
for voltage input
Maximum 0.5 mA continuous;
•
For current input
Maximum 50 mA continuous;
Connection of signal encoders
•
For voltage measurement
Possible
•
For current measurement
As 2-wire measuring
transducer
Possible, with external power supply
As 4-wire measuring
transducer
Possible
•
For measuring resistance
With 2-wire connection
Possible, without cable resistance compensation
With 3-wire connection
Not possible
With 4-wire connection
Not possible
Linearization of characteristic
curve
By software
•
For resistive thermometer
Pt 100
Temperature compensation
No
Technical unit for temperature
measurement
Degrees Centigrade/Fahrenheit/Kelvin
Содержание SIMATIC C7-635
Страница 12: ...Document Guide 1 2 C7 635 Control System A5E00155581 04 ...
Страница 14: ...Product Overview 2 2 C7 635 Control System A5E00155581 04 Figure 2 2 C7 635 Key ...
Страница 48: ...Installing and Wiring the C7 635 3 26 C7 635 Control System A5E00155581 04 ...
Страница 58: ...Special Features of the C7 635 4 10 C7 635 Control System A5E00155581 04 ...