Maintenance
5-4
C7-635 Control System
A5E00155581-04
Installation
Step
Action
1.
Complete the mechanical installation as described in Section 3.2. Be sure to
observe the relevant notes.
2.
Insert the MMC.
3.
Insert the cables and press the bare cables into the shielding terminals, as
4.
Switch on the power supply.
5.
Connect the C7-635 to the MPI interface of the programming device/PC.
6.
Make sure that in the “Control Panel” in the menu “Transfer > Transfer Settings”
the MPI interface is activated.
7.
Activate the transfer mode and download the backed-up TP/OP configuration
with ProTool.
8.
Clear and reset the C7-CPU.
9.
Switch the CPU to RUN mode.