Communications support modules
Hardware - SIMADYN D
6-13
Edition 12.2004
6
The CP1470 can be reset using the
reset button
. The switch must first be
set to "ADM".
Green Red
Significance
Dark
Dark
No power supply;
temporary initialization status
Lit
Dark
Database and synchronization O.K.
Flashi
ng
Dark Database
inconsistent; correct NML configuring
Dark
Lit
No synchronization with the initializing CPU module;
possible cause: @CSH11 function block not configured,
incorrect slot or incompatible firmware
Dark Flashin
g
Hardware fault
Flashi
ng
Lit
Switch in the STOP setting or ADM
The function of the LEDs is also described in the User Instructions
„Configuring the communications“.
6.2.1 Application information and noise immunity
•
the module may only be used in
forced-ventilated
subracks.
•
the serial connecting cables must be latched-in using the latching
mechanisms provided.
•
noise-immune operation is only possible if the module is tightly screwed
into the subrack
Further information on EMC and ambient conditions, refer to Section
„General technical data“.
6.2.2 Connector assignment of the interfaces
25-pin sub D socket connector
Pin RS-232 TTY
1 Screen
----
2 TxD ----
3 RxD ----
7 Ground
----
9 ---- +RxD
10 ----
-RxD
18 ----
+TxD
21 ----
-TxD
Reset button
LED
Other information
Parameterizing
interface X5